e-Mail to SCHMIDT Technology

  SS 20.515/516 SS 20.515/516 SS 20.400 / 23.400 SS 20.415 SS 20.500
Product code SS 20.250 SS 20.515 / 516 SS 20.400 / SS 23.400 SS 20.415 SS 20.500
Application Filter monitoring, supply and exhaust control Filter monitoring, Room monitoring Flow direction (turbulence degree) Flow direction (turbulence degree) Filter monitoring, Room monitoring if corrosive medias are present
Sensor head Dumb-bell head Dumb-bell head Thermopile head Thermopile head Dumb-bell head
Measuring range 0,06 … 20 m/s 0,06 … 10 m/s 0,05 … 20 m/s 0,05 … 20 m/s 0,06 … 35 m/s
Medium temperature -20 ... +70 °C 0 ... +60 °C 0 … +60 °C 0 … +60 °C -20 … +85 °C
Moistness area 0 ... 95 % rF 0 ... 95 % rF 0 ... 95 % rF 0 ... 95 % rF 0 ... 95 % rF
Specials

SS 20.515 for disinfection with
H2O2 (VHP)
 

SS 20.515 for disinfection with
H2O2 (VHP)
 
SS 20.516 for disinfection with alcohol (with coating)

Bi-directional flow sensor
Switching outputs
Measurement of turbulence degree
Self monitoring function
Detection of contamination ATEX version for Ex-secured areas
Disinfection with H2O2 and alcohols
Bi-directional flow sensor
Switching outputs
Measurement of turbulence degree
Self monitoring function Detection of contamination
Disinfection with H2O2 and alcohols
Protection against corrosion e.g.:
- hydrochloric acid
- caustic soda
- acetone
High precision adjustment
Mounting Mounting lengths from 300 / 500 mm available Screwed bush
M25 (stainless steel)
Quick mounting system
- Counternut
- Screw adapter
- Shank nut
- Flange bushing
Easy one-hole-mounting Screwed bush
M25 (stainless steel)
Quick mounting system
- Counternut
- Screw adapter
- Shank nut
- Flange bushing
Mounting lengths from 100 to 1.000 mm available
Output signals Auto UI
4 … 20 mA ↔
0 … 10 V
0 ... 10 V
4 ... 20 mA
0 ... 2 V
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
4 ... 20 mA
Auto UI
4 … 20 mA ↔
0 … 10 V
clean room
 

SCHMIDT® Flow Sensors for Cleanroom

For measurements in cleanrooms the thermic SCHMIDT® Flow Sensors provide many benefits:

  • Direct detection of flow velocity from 0.05 m/s
  • Cleanroom suitable – no moving parts, no grit (IP65 – IP67 degree of protection)
  • „Hygienic Design“ – easy cleanable dumb-bell head, disinfectable, hydrogen-peroxide resistant, suitable for VHP (Vaporized Hydrogen Peroxide) -method
  • In compliance with requirements of ISO 14644 regarding measuring range
  • „Bi-directional sensor“ enables the identification of over flow direction even during decrease of pressure
  • ISO-calibration protocol available – enables requirements of pharmaceutical industry
  • Easy to integrate in monitoring systems through variable data interfaces
  • Corrosion protection, resistant against aggressive process media (acid, brine, solvent)

Which sensor is suitable for which application?
There are special SCHMIDT® Flow Sensors for use in cleanroom and hygienic environments available:

Application examples:

Cleanroom supervision – monitoring

  • Detection of flow velocity, supervision of filter leakage, control of flow velocity
  • Detection of turbulence degree for estimation of laminarity of cleanroom flow
  • Supervision of flow direction (in case of decrease of pressure or reduction of flow velocity beyond production times

Energy saving and efficiency through

Higher measurement accuracy for efficient reduction of the flow velocity beyond production times (higher accuracy compared to stationed pressure measurement)

Plant monitoring

  • Supervision of plant integrated filter units
  • Control of exhaustion processes with corrosive media
  • Determination of turbulence degrees within one plant

Pharmaceutical Industry

  • Integration in cleanroom-monitoring (Annex1 GMP-guidelines)
  • Charge release in case of decrease of pressure through documentation of flow direction

Semi-conductor Industry

  • Flow monitoring if corrosive process media is present
  • Filter monitoring in clean machines
 
   
Application Report
- Flowbox
- CD Coating
- Labor. exhaust air
- Cleanrooms
 
Flow Calculator  
SCHMIDT® LED-Messwertanzeige MD 10.010/10.015
SCHMIDT® LED measured value display
MD 10.010/10.015
 
Datenschutz